ongoing2025 – present

Dynamic system modeling of liquid-cooled AI data centers

The first chip-to-ambient transient model of a direct-to-chip liquid-cooled AI rack, run under real workloads and real weather.

Simscape FluidsControl designStiff DAE solversSystem identificationHPC batch campaignsEnergy metrics (TUE, PUE)Reliability modeling

Why dynamics

Data centers used about 415 TWh in 2024, roughly 1.5 % of global electricity, and cooling is around a third of a facility’s energy. Rack density has jumped from under 10 kW to 130 kW for a GB200 NVL72, and programs such as ARPA-E COOLERCHIPS target racks above 126 kW cooled with at most 5 % of IT load. Air cannot do that; direct-to-chip liquid cooling is the default.

Nearly all of the modeling behind those systems is steady state, and the two industry metrics, PUE and TUE, are steady-state constructs. But AI training swings facility power at 0.2–3 Hz, inference has 1.7–2.8× diurnal peaks, weather acts directly on the dry cooler, and grids increasingly want data centers to shed load on request. Warm-water-cooled chips throttle within tens of seconds of losing flow. Nobody had a rack-scale, chip-to-ambient transient model, and nobody had a formal transient metric.

The model

Built in MATLAB Simscape Fluids: about 37 000 blocks and 580 logged signals covering 126 compute packages, cold plates, 14 modular in-rack coolant distribution units (gear pump plus brazed-plate heat exchanger), 532 quick disconnects, a glycol primary loop and two dry coolers in series, with 16 PI control loops. The chip side is a four-node RC chain per package validated against a bench GPU transient to 0.57 K RMSE; the cold plate is the lab’s measured diamond pin-fin dataset; the dry cooler is calibrated to manufacturer duty and checked out of sample. A 56-check conservation audit runs on every result.

Around the model sits a transient performance framework: a temperature-budget regime map (actuator floor, regulated, saturated), an inventory of storage and transport time scales from the die at under a millisecond to loop turnover at minutes, six excitation families with protocol rules, and a four-axis scorecard covering thermal compliance with JEDEC and ASHRAE rate limits, windowed TUE split into static and dynamic excess, frequency response, and cycling wear.

The campaign so far: 215 cases and more than 1 000 wall-hours on a 96-core node, including 77 realistic AI workload days and 24 week-long runs under measured Champaign and Austin weather.

What it answers

The results are in write-up for the International Journal of Heat and Mass Transfer, so the numbers stay in the paper for now. The shape of the findings:

  • Capacity derates linearly with ambient, and faster than a one-sided estimate, because the coolant supply temperature must fall with load.
  • The plant settles in about two minutes. A measured steady-state map plus an integral therefore predicts a full week’s cooling energy to about one percent, which is the licence to size from steady data.
  • A fluctuating load costs real energy versus a steady one at the same mean, and nearly all of that cost is curvature of the fan power curve rather than lag. Load smoothing, not faster control, is the lever.
  • Pumps, not fans, dominate cooling power in this warm-water architecture.
  • Demand-response sheds are thermally free; only the restore ramp matters, and a ten-minute ramp complies everywhere.
  • A climate-based sizing rule and an annual lookup that replaces thousands of wall-hours of simulation.

A gray-box reduced-order model built with a colleague runs 20–100× faster, and a pilot pumped two-phase loop with R1233zd(E) is the first step toward the same analysis for two-phase direct-to-chip cooling.

Status

First-author manuscript in preparation with seven co-authors. Presented to Gamma Technologies, Trane and A. O. Smith in 2026, and at ACRC meetings.